Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 997570.015
Citation: 03001
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/27/2015
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity:
Report ID: 0419400
Contest Date:
Final Order: 03/12/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/12/2015 | $0.00 | Other | ||
Penalty | Z: Issued | 02/27/2015 | $0.00 | Other |
Text For Citation: 03 Item/Group: 001 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) 414 CR 2790 in Guntown, MS - On or about October 7, 2014, in the shipping department, the flexible cord on a 42 inch diameter fan on the floor had a defective strain relief on the plug end and where the cord entered the fan housing.