Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1419071.015
Citation: 03001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $818.00
Current Penalty: $410.00
Issuance Date: 12/04/2019
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 12/23/2019
Gravity:
Report ID: 0418100
Contest Date:
Final Order: 12/31/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/31/2019 | $410.00 | 12/23/2019 | Other | |
Penalty | Z: Issued | 12/04/2019 | $818.00 | 12/23/2019 | Other |
Text For Citation: 03 Item/Group: 001 Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." On or about 7/30/2019 at the electrical panels, workers turning the fluorescent overhead lighting on and off daily were exposed to electrical hazards of up to 480 V where the 277 V breakers were not designed for daily use.