Violation Detail
Standard Cited: 19100303 G01 I A General.
This violation item has been deleted.
Inspection Nr: 1252926.015
Citation: 03001
Citation Type: Other
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/19/2018
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 02/14/2018
Gravity:
Report ID: 0418100
Contest Date: 02/12/2018
Final Order: 03/14/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 03/14/2019 | $0.00 | 02/14/2018 | Other | |
| Penalty | C: Contested | 02/15/2018 | $0.00 | 02/14/2018 | Other | |
| Penalty | Z: Issued | 01/19/2018 | $0.00 | 02/14/2018 | Other |
Text For Citation: 03 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910. On 8/1/17, at the Gainesville, Georgia facility, in the MSC Room, the working space in front of the knife switch/disconnect for the MSC debone machine was 16 inches.