Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 1542164.015
Citation: 02035
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,827.00
Current Penalty: $3,000.00
Issuance Date: 01/06/2022
Nr Instances: 5
Nr Exposed: 9
Abatement Date: 02/24/2022
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 02/11/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/11/2022 | $3,000.00 | 02/24/2022 | Serious | |
Penalty | Z: Issued | 01/06/2022 | $6,827.00 | 02/24/2022 | Serious |
Text For Citation: 02 Item/Group: 035 Hazard:
29 CFR 1910.304(g)(5):The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: A. Plastics Department, Drill press workstation located next to machine #311: On, or about, July 28, 2021, the following equipment did not have a continuous path to ground: 1. Relocatable power tap energizing the Craftsman drill press and the overhead work light. 2. The Craftsman drill press was missing the ground prong on the plug. B. Thermoset Department, Machine 307: On, or about, July 28, 2021, the receptacle provided on the back of Machine #307 showed an open ground when tested. The receptacle was used to energize a work light at Machine #308. C. Metal Department, Tumbling Area: On, or about, August 6, 2021, a yellow Maxx Air fan was missing the ground pin on the plug connection. D. Maintenance Shop: On, or about, September 2, 2021, the light fixture provided at the Boyar-Shultz surface grinder was energized through an extension cord that was missing the ground prong.