Violation Detail
Standard Cited: 19100305 B03 I Wiring methods, components, and equipment for general use.
Inspection Nr: 980283.015
Citation: 02008A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,500.00
Current Penalty: $5,500.00
Issuance Date: 12/09/2014
Nr Instances: 2
Nr Exposed: 7
Abatement Date: 12/29/2014
Gravity: 5
Report ID: 0626700
Contest Date: 01/12/2015
Final Order: 09/02/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | R: Review Commission | 09/02/2015 | $5,500.00 | 12/29/2014 | Serious | |
| Penalty | C: Contested | 01/13/2015 | $5,500.00 | 12/29/2014 | Serious | |
| Penalty | Z: Issued | 12/09/2014 | $5,500.00 | 12/29/2014 | Serious |
Text For Citation: 02 Item/Group: 008A Hazard:
29 CFR 1910.305(b)(3)(i): Pull and junction boxes used on systems rated over 600 volts, nominal, did not provide a complete enclosure for the contained conductors or cables: a) At Control Room C, isle 1, the employer did not effectively close an unused opening on the General Electric 13,800 Volts Box, exposing employees to electrical hazards. b) At Control Room C, isle 2, the employer did not effectively close an unused opening on the General Electric 13,800 Volts Box, exposing employees to electrical hazards.