Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1446527.015
Citation: 02008
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/17/2020
Nr Instances: 1
Nr Exposed: 50
Abatement Date: 05/06/2020
Gravity:
Report ID: 0111700
Contest Date:
Final Order: 05/11/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/11/2020 | $0.00 | 05/06/2020 | Other | |
Penalty | Z: Issued | 04/17/2020 | $0.00 | 05/06/2020 | Other |
Text For Citation: 02 Item/Group: 008 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. Paper Machine #9- Employees were not protected from an electric shock hazard where circuit breakers inside LPPN 3-22-1 panel board were not adequately labeled to identify their purpose. b. Lift Station- Employees were not protected from an electric shock hazard where circuit breakers inside LPPN 26-1 panel board were not adequately labeled to identify their purpose. c. T&T Warehouse- Employees were not protected from an electric shock hazard where circuit breakers inside PDPN #1-1 and PDPN #1-2 panel boards were not adequately labeled to identify their purpose.