Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1208858.015
Citation: 02006
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/13/2017
Nr Instances: 2
Nr Exposed: 200
Abatement Date:
Gravity:
Report ID: 0521400
Contest Date: 08/07/2017
Final Order: 08/01/2018
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/01/2018 | $0.00 | Other | ||
Penalty | C: Contested | 08/08/2017 | $0.00 | Other | ||
Penalty | Z: Issued | 07/13/2017 | $0.00 | Other |
Text For Citation: 02 Item/Group: 006 Hazard:
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: On or about 22 February 2017, the employer failed to adequately mark branch circuit disconnects to indicate their intended purpose at Module #2 west side at aisle #20 and Aisle #52. These branch circuit disconnects control the roof exhaust fans. There are numerous disconnects throughout the facility that are not marked. This exposed employees to a shock or struck-by hazard due to employees not knowing what disconnects to turn off in case of maintenance or emergency. Abatement is not required for this item.