Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 922729.015
Citation: 02005
Citation Type: Repeat
Abatement Status: Abatement Completed
Initial Penalty: $22,000.00
Current Penalty: $22,000.00
Issuance Date: 01/22/2014
Nr Instances: 16
Nr Exposed: 6
Abatement Date: 02/06/2014
Gravity: 5
Report ID: 0317900
Contest Date:
Final Order: 02/10/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/10/2014 | $22,000.00 | 02/06/2014 | Repeat | |
| Penalty | Z: Issued | 01/22/2014 | $22,000.00 | 02/06/2014 | Repeat |
Text For Citation: 02 Item/Group: 005 Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed. a) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, two separate conductors entering the # 1 boiler control panel were not protected from abrasions. P7240017, 35 b) Philadelphia Macaroni Company, Warehouse. - On or about July 26, 2013, conductors entering the conduit on a wall adjacent to the forklift area were not protected from abrasions. P7260048 c) Philadelphia Macaroni Company Warehouse. - On or about July 26, 2013, conductors entering the conduit connected to a switch gear box behind a forklift charger in the forklift area were not protected from abrasions. P7260056 d) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, an unused opening in a metal 4 inch knock out box on the #1 boiler was not effectively closed. P7240005 e) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, an unused opening on the left side of the on the #1 boiler control panel was not effectively closed. P7240034 f) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, an unused opening in a metal 4 inch knock out box on the #2 boiler was not effectively closed. P7240004 g) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, an unused knock out opening in a metal control box on the #2 boiler was not effectively closed. P7240008 h) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, an unused opening on the door of a metal switch box was not effectively closed. P7240025 i) Philadelphia Macaroni Company, Boiler Room. - On or about July 24, 2013, an unused opening in a metal 2 inch knock out box behind the boilers was not effectively closed. P7240076 j) Philadelphia Macaroni Company, Maintenance Room. - On or about July 24, 2013, unused opening on the left side of a breaker switch box was not effectively closed. P7240055 k) Philadelphia Macaroni Company, Maintenance Room. - On or about July 26, 2013, an unused opening on the right side of a knife switch box powering the triple light bulbs was not effectively closed. P7260029 l) Philadelphia Macaroni Company, Warehouse. - On or about July 24, 2013, an unused opening on the right side of a metal cable tray on the wall adjacent to the forklift area was not effectively closed. P7260054 m) Philadelphia Macaroni Company, Warehouse. - On or about July 26, 2013, an unused opening on the left side of a 4 inch metal box on a wall adjacent to the forklift area was not effectively closed. P7260048 n) Philadelphia Macaroni Company, Warehouse. - On or about July 26, 2013, an unused opening on the left side of a 4 inch receptacle box powering the scale in the forklift charging area was not effectively closed. P7260060 o) Philadelphia Macaroni Company, Press Room. - On or about July 26, 2013, an opening caused by a pushed in power light on #3 mixing unit was not effectively closed. P7260124 p) Philadelphia Macaroni Company, #7 Use Bin. - On or about September 24, 2013, an unused opening on the right side of an ITE Brand enclosed metal switch box was not effectively closed. Philadelphia Macaroni was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(1), which was contained in OSHA inspection number 311269377, citation number 1, item number 5a and was affirmed as a final order on November 5, 2008, with respect to a workplace located at 40 Jacksonville Road Warminster, PA 18974.
Translate