Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 1366023.015
Citation: 02004B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $8,525.00
Current Penalty: $0.00
Issuance Date: 04/03/2019
Nr Instances: 7
Nr Exposed: 100
Abatement Date: 04/22/2019
Gravity: 5
Report ID: 0111700
Contest Date: 04/23/2019
Final Order: 04/27/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/27/2022 | $0.00 | 04/22/2019 | Other | |
Penalty | C: Contested | 04/26/2019 | $8,525.00 | 04/22/2019 | Serious | |
Penalty | Z: Issued | 04/03/2019 | $8,525.00 | 04/22/2019 | Serious |
Text For Citation: 02 Item/Group: 004B Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Rough Mill, Milling, Plywood Area- Employees operating woodworking equipment were not protected from electrical hazards where overcurrent devices, electric disconnects, and panel boards were not readily accessible due the working space in front of and below the equipment being used for storage. The electric equipment included the following: 1. 480 volt panel board next to the quad press 2. Two 480 volt panel boards near the Koch bore and dowel machine 3. Two 600 Volt electric disconnects near the Koch bore and dowel machine 4. 208 volt panel board near the panel saws 5. 208 volt fan disconnect next to the panel saws 6. 480 volt PP-1 panel board in the maintenance garage