Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1469050.015
Citation: 02004
Citation Type: Other
Abatement Status: Not Completed - AD Discretion
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/10/2020
Nr Instances: 1
Nr Exposed: 14
Abatement Date: 05/08/2020
Gravity:
Report ID: 0636900
Contest Date:
Final Order: 05/11/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 04/10/2020 | $0.00 | 05/08/2020 | Other |
Text For Citation: 02 Item/Group: 004 Hazard:
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: In the warehouse, the employer did not ensure that the 100 amps electrical box had a cover exposing employees to an electrical hazard.