Violation Detail
Standard Cited: 19100037 B06 Maintenance, safeguards, and operational features for exit routes.
Inspection Nr: 1462337.015
Citation: 02004
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/24/2020
Nr Instances: 1
Nr Exposed: 25
Abatement Date: 04/30/2020
Gravity:
Report ID: 0521400
Contest Date:
Final Order: 04/13/2020
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/13/2020 | $0.00 | 04/30/2020 | Other | |
Penalty | Z: Issued | 03/24/2020 | $0.00 | 04/30/2020 | Other |
Text For Citation: 02 Item/Group: 004 Hazard:
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted. South, emergency exit door between dock doors No. 30 and No. 31: on or about February 12, 2020, employees working in the area were exposed to delayed emergency evacuation hazards associated with a hardwired EXIT sign that was not illuminated. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(c).