Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1246712.015
Citation: 02004
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/01/2017
Nr Instances: 3
Nr Exposed: 1
Abatement Date: 11/09/2017
Gravity:
Report ID: 0418600
Contest Date:
Final Order: 01/05/2018
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/05/2018 | $0.00 | 11/09/2017 | Other | |
| Penalty | Z: Issued | 11/01/2017 | $0.00 | 11/09/2017 | Other |
Text For Citation: 02 Item/Group: 004 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Main Fan Room: On or about July 13, 2017 and at times prior to, the employer exposed employees to electrical burns, shock and fire hazards from a 4 to 20 milliamp electrical box housing signal feedback wiring that was not effectively closed. b) Main Fan Room: On or about July 13, 2017 and at times prior to, the employer exposed employees to electrical burns, shock and fire hazards from a 4 to 20 milliamp electrical box housing signal fan bearing temperature relay wiring that was not effectively closed. c) Bag House Area: On or about July 13, 2017 and at times prior to, the employer exposed employees to electrical burns, shock and fire hazards from a 24 volt electrical box housing control wiring to rotary valve that was not effectively closed.