Violation Detail
Standard Cited: 19100303 B01 VII General.
Inspection Nr: 1040901.015
Citation: 02004
Citation Type: Other
Abatement Date: 05/19/2015 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/23/2015
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity:
Report ID: 0524500
Contest Date:
Final Order: 05/13/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/13/2015 | $0.00 | 05/19/2015 | Other | |
Penalty | Z: Issued | 04/23/2015 | $0.00 | 05/19/2015 | Other |
Text For Citation: 02 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(1)(vii): Safety of equipment was not determined using considerations for classification by type, size, voltage, current capacity, or specific use. Employees were exposed to minor electrical shock from a 120V/20A circuit breaker used to switch the door alarm circuits daily and the circuit breaker was not rated for switch duty.