Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
Inspection Nr: 313796732
Citation: 02003D
Citation Type: Willful
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 07/07/2010
Nr Instances: 2
Nr Exposed: 226
Abatement Date: 12/31/2010
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/30/2010 | 12/31/2010 | Willful | ||
| Penalty | Z: Issued | 07/07/2010 | 11/15/2010 | Willful |
Text For Citation: 02 Item/Group: 003D Hazard: CHEMNEP
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment to maintain its mechanical integrity, was not consistent with applicable manufacturers' recommendations and good engineering practices, or more frequently determined to be necessary by prior operating experience: a)Facility: The employer did not conduct inspections and tests on compressors to the frequency consistent with good engineering practices. Good engineering practices for the compressors include: 1. Annually inspected inspect drive alignment, foundation bolts, and drive shaft end float on compressors. 2. Annually test compressor protection devices and cutouts, such as such as high pressure and low pressure cutouts, oil pressure differential switches, and oil temperature cutouts b) Facility: The employer did not conduct inspections and tests of evaporative condensers to the frequency consistent with good engineering practices. Good engineering practices for the evaporative condensers include: 1. Clean pan strainer and check bleed-off valve for proper operation weekly. 2. Clean and flush pan, check operating level in pan, and adjust float valve monthly.
Translate