Violation Detail
Standard Cited: 19100119 J05 Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 311611081
Citation: 02003B
Citation Type: Willful
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/08/2010
Nr Instances: 1
Nr Exposed: 25
Abatement Date: 04/19/2010
Gravity: 10
Report ID: 0524700
Contest Date: 03/31/2010
Final Order: 09/27/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | D: Govt Dismissed | 09/27/2018 | $0.00 | Willful | ||
Penalty | Z: Issued | 03/08/2010 | $0.00 | Willful |
Text For Citation: 02 Item/Group: 003B Hazard: REFINERY
29 CFR 1910.119(j)(5): The employer does not correct deficiencies in equipment that are outside acceptable limits (as defined by process information in 29 CFR 1910.119(d) before further use or in a safe and timely manner: a.BP-Husky Refini ng, LLC - Oregon, Ohio: The employer does not ensure PSV-137, located in the Alk y Unit, has an inlet pressure drop of not more than 3 PSV-137 was determined to have an inlet pressure drop of 4.6 Pursuant to 29 CFR 1903.19, within ten (10) c alendar days of the abatement date, the employer must submit documentation that it has abated the hazard. In addition, under 29 CFR 1903.19(e), the employer sha ll submit an abatement plan describing the actions it is taking to ensure that i t is in compliance with the standards including documentation that each pressure relief valve and associated piping for all process units have been evaluated an d, if necessary, repaired or replaced to ensure inlet pressure drop is limited i n accordance with recognized and generally accepted good engineering practices, such as API Recommended Practice 520 and the ASME Bo iler and Pressure Vessel Code. The abatement plan shall establish dates during t he next three months when the evaluations, repairs, and replacements shall be co mpleted. Once the plan has been fully implemented, the employer must submit cert ification of its full compliance with the standard.e