Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1366023.015
Citation: 02003B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $8,525.00
Current Penalty: $0.00
Issuance Date: 04/03/2019
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 04/09/2019
Gravity: 5
Report ID: 0111700
Contest Date: 04/23/2019
Final Order: 04/27/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/27/2022 | $0.00 | 04/09/2019 | Other | |
Penalty | C: Contested | 04/26/2019 | $8,525.00 | 04/09/2019 | Serious | |
Penalty | Z: Issued | 04/03/2019 | $8,525.00 | 04/09/2019 | Serious |
Text For Citation: 02 Item/Group: 003B Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: Rough Mill- Employees operating the gang saw and feed conveyor after the gang saw were not protected from an electric shock hazard where a 240 volt flexible cable connected to a foot pedal for an electric lift table did not have strain relief where the conductors were spliced to the control pedal. The foot pedal was open in the back with the spices from the conductors of the cable to control pedal exposed.