Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 1702846.015
Citation: 02003
Citation Type: Other
Abatement Date: 12/27/2023 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/15/2023
Nr Instances: 1
Nr Exposed: 11
Related Event Code (REC):
Gravity:
Report ID: 0936200
Contest Date:
Final Order: 12/12/2023
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/12/2023 | $0.00 | 12/27/2023 | Other | |
Penalty | Z: Issued | 11/15/2023 | $0.00 | 12/27/2023 | Other |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Maintenance Room, next to the rebuild tooling cabinet: On and/or before October 11, 2023, the employer did not ensure at least 3 feet in front of the electrical panel and switch box was clear. The circuit breaker had a tool cabinet and clothing obstructing the panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).