Violation Detail
Standard Cited: 19100110 B06 II Storage and handling of liquefied petroleum gases.
Inspection Nr: 1690199.015
Citation: 02003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,578.00
Current Penalty: $7,300.00
Issuance Date: 01/24/2024
Nr Instances: 1
Nr Exposed: 23
Abatement Date: 10/23/2024
Gravity: 5
Report ID: 0317700
Contest Date:
Final Order: 02/12/2024
Related Event Code (REC):
Emphasis:
Substance: 2150
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/12/2024 | $7,300.00 | 10/23/2024 | Serious | |
Penalty | Z: Issued | 01/24/2024 | $10,578.00 | 04/23/2024 | Serious |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.110(b)(6)(ii): Each individual container was not located the minimum specified distance from an important building or group of buildings in accordance with Table H-23: a) Roundhouse Building: A 26,000 gallon liquid propane tank was installed less than 50 feet from an important building, exposing employees to fire and explosion hazards, on or about August 10, 2023. ABATEMENT CERTIFICATION REQUIRED