Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1686804.015
Citation: 02003
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/23/2024
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 02/21/2024
Gravity:
Report ID: 0418200
Contest Date:
Final Order: 02/20/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/20/2024 | $0.00 | 02/21/2024 | Other | |
Penalty | Z: Issued | 01/23/2024 | $0.00 | 02/21/2024 | Other |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Production Floor: On or about July 31, 2023, and at times prior, the employer exposed employees to electrical and fire hazards, in that electrical conductors, supplying power to the air compressor, were run through flexible metal conduit and into a wall mounted electrical junction box where the conduit was not connected to the box which would have provided strain relief to the terminal connections of these conductors.