Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1682467.015
Citation: 02003
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/28/2023
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 08/23/2023
Gravity:
Report ID: 0936200
Contest Date:
Final Order: 08/28/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/28/2023 | $0.00 | 08/23/2023 | Other | |
| Penalty | Z: Issued | 07/28/2023 | $0.00 | 08/23/2023 | Other |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On and/or before July 11, 2023, the employer did not ensure each circuit breaker was legibly marked to indicate its purpose in the electrical panels. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s). In the following locations: a) Laundry room b) Wall across from the electrical room