Violation Detail
Standard Cited: 19100303 G01 I A General.
This violation item has been deleted.
Inspection Nr: 1541509.015
Citation: 02003
Citation Type: Other
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/06/2022
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 02/02/2022
Gravity:
Report ID: 0523400
Contest Date: 02/01/2022
Final Order: 01/17/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/17/2023 | $0.00 | 02/02/2022 | Other | |
Penalty | C: Contested | 02/23/2022 | $0.00 | 02/02/2022 | Other | |
Penalty | Z: Issued | 01/06/2022 | $0.00 | 02/02/2022 | Other |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.303(g)(1)(i)(A):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: (a) On or about August 3, 2021, at the worksite located at 714 E. Keefe Ave, Milwaukee WI, the employer did not ensure the depth of the working space in front of an electrical cabinet connected to, at minimum, the Extruder # 1 machine, met the distance indicated in Table S-1 of Subpart S of 1910, thereby exposing workers to electrical hazards. (b) On or about August 3, 2021, at the worksite located at 714 E. Keefe Ave, Milwaukee WI, the employer did not ensure the depth of the working space in front of an electrical cabinet connected to, at minimum, the Formex 2000 machine, met the distance indicated in Table S-1 of Subpart S of 1910, thereby exposing workers to electrical hazards.