Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1323224.015
Citation: 02003
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/07/2018
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 01/04/2019
Gravity:
Report ID: 0418200
Contest Date:
Final Order: 01/04/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/04/2019 | $0.00 | 01/04/2019 | Other | |
Penalty | Z: Issued | 12/07/2018 | $0.00 | 01/04/2019 | Other |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Engine Room 1, Engine Room 3; On or about June 12, 2018, and at times prior, the employer exposed employees to fire hazards in that fans, lights, and compressors were plugged into flexible cords rather than a fixed wired outlet. b) Chemical Room; On or about June 12, 2018, and at times prior, the employer exposed employees to fire hazards in that sensors were plugged into an extension cord rather than a fixed wired outlet.