Violation Detail
Standard Cited: 19100037 B06 Maintenance, safeguards, and operational features for exit routes.
Inspection Nr: 1293344.015
Citation: 02002C
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/10/2018
Nr Instances: 1
Nr Exposed: 12
Abatement Date: 02/11/2019
Gravity:
Report ID: 0521400
Contest Date: 08/31/2018
Final Order: 01/09/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 01/09/2019 | $0.00 | 02/11/2019 | Other | |
| Penalty | C: Contested | 09/06/2018 | $0.00 | 09/17/2018 | Serious | |
| Penalty | Z: Issued | 08/10/2018 | $0.00 | 09/17/2018 | Serious |
Text For Citation: 02 Item/Group: 002C Hazard:
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted. On or about 14 February 2018, the employer did not ensure that each exit sign was illuminated to the required surface value. This exposed employees to injury from smoke inhalation or burn in case of a fire. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).