Violation Detail
Standard Cited: 19100119 F01 Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1194726.015
Citation: 02002A
Citation Type: Repeat
Abatement Date: 06/12/2017
Initial Penalty: $49,797.00
Current Penalty: $0.00
Issuance Date: 05/08/2017
Nr Instances: 7
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0216000
Contest Date: 05/25/2017
Final Order: 02/07/2019
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/07/2019 | $0.00 | 06/12/2017 | Repeat | |
Penalty | C: Contested | 05/31/2017 | $49,797.00 | 06/12/2017 | Repeat | |
Penalty | Z: Issued | 05/08/2017 | $49,797.00 | 06/12/2017 | Repeat |
Text For Citation: 02 Item/Group: 002A Hazard:
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities in each covered process consistent with process safety information and which addressed at least the following 1910.119(f)(1)(i) through 1910.119(f)(1)(iv): a) Engine Room - Vogt Ice Maker IM-5: The operating procedures for running Vogt Ice Maker IM-5 were unsafe as they incorrectly indicated that the maximum operating limit pressure was 275 psig when the maximum allowable working pressure on the vessel was 200 psig; on or about 11/14/16. b) Engine Room - Vogt Ice Maker IM-6: The operating procedures for running Vogt Ice Maker IM-6 were unsafe as they incorrectly indicated that the maximum operating limit pressure was 275 psig when the maximum allowable working pressure on the vessel was 200 psig; on or about 11/14/16. c) Engine Room - Vogt Ice Maker IM-7: The operating procedures for running Vogt Ice Maker IM-7 were unsafe as they incorrectly indicated that the maximum operating limit pressure was 275 psig when the maximum allowable working pressure on the vessel was 200 psig; on or about 11/14/16. d) Engine Room - Vogt Ice Maker IM-8: The operating procedures for running Vogt Ice Maker IM-8 were unsafe as they incorrectly indicated that the maximum operating limit pressure was 275 psig when the maximum allowable working pressure on the vessel was 200 psig; on or about 11/14/16. e) Engine Room: The operator was required to use a portable ammonia direct-reading instrument when entering the engine room and when performing oil draining from the receiver located in a pit in the engine room. The employer did not develop and implement written operating procedures to ensure that the portable ammonia direct-reading instrument was worn properly, calibrated, tested, and not missing any parts; on or about 11/14/16. f) Entire Covered Process - Engine Room, Freezer Room and Rooftop Areas: The employer did not implement operating procedures to conduct daily refrigeration rounds of covered process equipment in accordance with equipment manufacturers' recommendations and standard operating procedures when the operator did not report to work on dates such as on or about 11/20/16 - 11/25/16; 12/12/16; 12/19/16; 12/21/16 - 12/23/16; 1/16/17 - 1/17/17; 2/1/17; 2/9/17; and 2/14/17; condition noted 11/14/16 through 2/14/17. g) Engine Room: Mycom Compressors RC-5 and RC-6: The operating procedure did not include a daily inspection of the compressor's suction pressure, oil supply pressure, suction temperature, discharge temperature and supply oil temperature were not inspected daily in accordance with the Mycom Instruction Manual for W-Series Reciprocating Compressors (April 2014 revision); on or about 11/14/16. REPEAT STATEMENT: Arctic Glacier U.S.A., Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29CFR 1910.119(f)(1), which was contained in OSHA inspection number 623559, citation number 1, item number 10a and was affirmed as a final order on June 28, 2013, with respect to a workplace located at 500 Fenimore Road, Mamaroneck, NY 10543