Violation Detail
Standard Cited: 19261052 C01 II Stairways.
Inspection Nr: 987635.015
Citation: 02002
Citation Type: Other
Abatement Status: Not Completed - AD Discretion
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/28/2015
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 02/03/2015
Gravity:
Report ID: 0316100
Contest Date:
Final Order: 02/24/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/28/2015 | $0.00 | 02/03/2015 | Other |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1926.1052(c)(1)(ii): Stairways having four or more risers or rising more than 30 inches (76 cm), whichever is less, were not equipped with a stairrail system along each unprotected side or edge: (a) Building 5312 - Workers was constructing a stairway with four risers and it did not have a stairrail system, on or about July 31, 2014. (b) Building 5310 - Workers were using a stairway with twelve risers to assess their work area on the upper floors and it did not have a stairrail system, on or about July 31, 2014. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Translate