Violation Detail
Standard Cited: 19100305 C04 Wiring methods, components, and equipment for general use.
Inspection Nr: 985908.015
Citation: 02002
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $850.00
Current Penalty: $500.00
Issuance Date: 12/05/2014
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 12/17/2014
Gravity:
Report ID: 0627500
Contest Date:
Final Order: 12/12/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 12/12/2014 | $500.00 | 12/17/2014 | Other | |
| Penalty | Z: Issued | 12/05/2014 | $850.00 | 12/17/2014 | Other |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface. On or July 15, 2014, and at times prior thereto, an electrolyte slime emergency alarm reset (ON/OFF) snap switch installed in a junction box at a pole outside the Supervisor's office did not have a cover plate that covered completely the electrical energized wires inside the box at the Slime/Leaching area. This condition exposed employees to electrical hazards.