Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 1696385.015
Citation: 02002
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/05/2023
Nr Instances: 1
Nr Exposed: 10
Abatement Date:
Gravity:
Report ID: 0112000
Contest Date:
Final Order: 01/12/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/12/2024 | $0.00 | Other | ||
| Penalty | Z: Issued | 12/05/2023 | $0.00 | Other |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Warehouse: On, or about, September 8, a small table was stored in front of two 120/208 volt panelboards, both labeled LP4.