Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1503927.015
Citation: 02002
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/21/2020
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 01/19/2021
Gravity:
Report ID: 0419700
Contest Date:
Final Order: 03/31/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/31/2022 | $0.00 | 01/19/2021 | Other | |
Penalty | Z: Issued | 12/21/2020 | $0.00 | 01/19/2021 | Other |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. On or about November 23, 2020, at the south wall of the service department, the opened 480-V electric panel had circuit breakers being used that were not marked to indicate their purpose, exposing employees to electrical hazards.