Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage shall be separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour. a) 1910 South Boulevard, Brewton, AL; On or about January 19, 2017 and at times prior, the employer exposed employees to fire hazards in that oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials such as acetylene as required.