Violation Detail
Standard Cited: 19100307 F03 Hazardous (classified) locations.
This violation item has been deleted.
Inspection Nr: 1075046.015
Citation: 02002
Citation Type: Other
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/13/2015
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 09/09/2015
Gravity:
Report ID: 1032500
Contest Date:
Final Order: 09/09/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/09/2015 | $0.00 | 09/09/2015 | Other | |
| Penalty | Z: Issued | 08/13/2015 | $0.00 | 09/09/2015 | Other |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.307(f)(3): The employer did not use dust-tight protection techniques for equipment in Class II, Division 2 and Class III locations. a) Circuit Breaker Panel, MCC #3, On or about July 1, 2015: Dust-tight protection techniques were not used for this circuit breaker panel rated at 480 Volts. Panel doors were open to the circuit breakers for the 50HP Saw, In Feed to Tom Dog, Bin Removal #2, and the Transfer to Turning Chains and Even End Roll. The panel is located in a Class III location. Abatement certification is required for this item.