Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1051410.015
Citation: 02002
Citation Type: Repeat
Abatement Date: 10/21/2015 2
Initial Penalty: $27,500.00
Current Penalty: $15,500.00
Issuance Date: 09/24/2015
Nr Instances: 4
Nr Exposed: 5
Related Event Code (REC):
Gravity: 5
Report ID: 0418400
Contest Date: 10/15/2015
Final Order: 08/08/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/08/2016 | $15,500.00 | 10/21/2015 | Repeat | |
Penalty | C: Contested | 10/27/2015 | $27,500.00 | 10/21/2015 | Repeat | |
Penalty | Z: Issued | 09/24/2015 | $27,500.00 | 10/21/2015 | Repeat |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about March 31, 2015 and times prior to: a) Pail Department, Compound Mixing Station - A duplex electrical receptacle designed to be mounted was taped to the pole of the hoist and was being used to power the hoist and a fan, thus exposing employees to electrical hazards. b) Pail Department, UN Cover Line - A quadplex electrical receptacle designed to be mounted was being used as a pendant to power hand tools, thus exposing employees to electrical hazards. On or about April 1, 2015 and times prior to: c) Ammo Department - A duplex electrical receptacle designed to be mounted was being used as a pendant to power drills and portable lights used to service the AMO 510P mechanical power press, thus exposing employees to electrical hazards. d) Paint Chain behind B-Line - A duplex electrical receptacle designed to be mounted was being used as a pendant to power fans and a parts washer, thus exposing employees to electrical hazards. Plastican A Division of Bway Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard [1910.303(b)(2)], which was contained in OSHA inspection number 314209461, citation number 1, item number 6 and was affirmed as a final order on September 1, 2011, with respect to a workplace located at 101 Lillian Drive, Macon, GA 31217.