Violation Detail
Standard Cited: 19100119 E03 III Process safety management of highly hazardous chemicals.
Inspection Nr: 313796732
Citation: 02001D
Citation Type: Willful
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 07/07/2010
Nr Instances: 4
Nr Exposed: 226
Abatement Date: 08/01/2011
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/30/2010 | 08/01/2011 | Willful | ||
| Penalty | Z: Issued | 07/07/2010 | 11/15/2010 | Willful |
Text For Citation: 02 Item/Group: 001D Hazard: CHEMNEP
29 CFR 1910.119(e)(3)(iii): The process hazard analysis did not address the engineering and administrative controls applicable to the hazards and their interrelationship: The employer failed to address engineering and administrative controls in the PHA such as: a)the ammonia detection system; b)continuously operating exhaust fans in refrigeration room in the absence of Class 1, Division II classification; c)emergency isolation valves such as King Valves; d)the mechanical integrity procedures for equipment, such as, but not limited to low and high pressure receiver, vertical accumulator, evaporators, dump tanks and piping.tors,