Violation Detail
Standard Cited: 19100119 E03 I Process safety management of highly hazardous chemicals.
Inspection Nr: 313796732
Citation: 02001B
Citation Type: Willful
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 07/07/2010
Nr Instances: 4
Nr Exposed: 226
Abatement Date: 08/01/2011
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/30/2010 | 08/01/2011 | Willful | ||
| Penalty | Z: Issued | 07/07/2010 | 11/15/2010 | Willful |
Text For Citation: 02 Item/Group: 001B Hazard: CHEMNEP
29 CFR 1910.119(e)(3)(i): The process hazard analysis (PHA) did not address the hazards of the process: The PHA did not address: a)hazards associated with a power failure; b)ammonia leaks due to corrosion of ammonia piping; c)hazards associated with not marking piping and equipment of the ammonia refrigeration system components; d)hazards associated with the loading operations, in which ammonia is added to the ammonia refrigeration system.ration
Translate