Violation Detail

Standard Cited: 19100119 D03 IB Process safety management of highly hazardous chemicals.

Inspection Nr: 315027292

Citation: 02001A

Citation Type: Serious

Abatement Status: X

Initial Penalty: $38,500.00

Current Penalty: $20,000.00

Issuance Date: 05/03/2011

Nr Instances: 15

Nr Exposed: 350

Abatement Date: 05/27/2011

Gravity: 10

Report ID: 1032500

Contest Date:

Final Order:

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 05/27/2011 $20,000.00 05/27/2011 Serious  
Penalty Z: Issued 05/03/2011 $38,500.00 05/27/2011 Repeat  

Text For Citation: 02 Item/Group: 001A Hazard: CHEMNEP

29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process does not include piping and instrument diagrams (P&IDs). a.Outside Ammonia High Pressure Storage Tanks: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6822-F-120.1, was not accurate since the P&ID indicated a pipe reduction from one inch to one-half inch and one-quarter inch at V-547. The pipe reduction did not exist in the field. b.Outside Ammonia High Pressure Storage Tanks: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6822-F-120.1, was not accurate since a pipe reduction from a three inch pipe near V-574 that was observed in the field, was not included on the P&ID. c.Outside Ammonia High Pressure Storage Tanks: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6822-F-120.1, was not accurate since the PV-042 on the P&ID was actually tagged as V-456 in the field. d.Outside Ammonia High Pressure Storage Tanks: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6822-F-120.1, was not accurate since the P&ID did not contain a label for a gate valve which was tagged as V-589 in the field. e.Outside Ammonia High Pressure Storage Tanks: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6822-F-120.1, was not accurate since the valves labeled as V-515 and V-514 on the P&ID, did not correspond to the identification tags observed in the field. f.Ammonia Low Pressure Storage: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6825-F-161.1, was not accurate since a pressure valve (PV) actuator located near V-067 on the P&ID did not exist in the field. g.Ammonia Low Pressure Storage: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-6825-F-161.1, was not accurate since V-067 on the P&ID was not located in the same location in the field. h.Ammonia Low Pressure Storage: On or about January 5, 2011 and at times prior thereto, the P&ID marked as JRS-6825-F-161.8, was not accurate since a gate valve shown on the Unloading Line, "3" AL-901-SLA-903" did not exist in the field. i.Ammonia Low Pressure Storage: On or about January 5, 2011 and at times prior thereto, the P&ID marked as JRS-6825-F-161.8, was not accurate since a threaded cap shown on the Unloading Line, "3" AL-901-SLA-903" did not exist in the field. j.Ammonia Low Pressure Storage: On or about January 5, 2011 and at times prior thereto, the P&ID marked as JRS-6825-F-161.8, was not accurate since the temperature indicator (TI) 6800-7349 was actually located downstream of thetemperature element (TE) 6800-7350 on "4" AL-901-SLA-903". k.Ammonia Low Pressure Storage: On or about January 5, 2011 and at times prior thereto, the P&ID marked as JRS-6825-F-161.8, was not accurate since a pipe reduction from three inches to one-quarter inch shown between V-056 and V-055 did not exist in the field. l.Ammonia Low Pressure Storage: On or about January 5, 2011 and at times prior thereto, the P&ID marked as JRS-6825-F-161.8, was not accurate since a temperature point (TP) shown at "AMMONIA XFER PUMP" "JRS-6825-F-161.1" was not labeled on the P&ID. m.Ammonia Low Pressure Storage: On or about January 5, 2011 and at times prior thereto, the P&ID marked as JRS-6825-F-161.8, was not accurate since a temperature point (TP) shown at "RELIEF HEADER" "JRS-6825-F-161.7" was not labeled on either side of the P&ID. n.Ammonium Phosphate Plant #100-Granualtion: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7011-F-122, was not accurate since valves labeled V-763 and V-764 on the P&ID, did not correspond to the identification tags observed in the field. o.Ammonium Phosphate Plant #100-Granualtion: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7011-F-122, was not accurate since the P&ID did not indicate a pipe containing a gate valve and check valve which were located between V-763 and V-764 in the field. p.Ammonium Phosphate Plant #100-Granualtion: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7011-F-122, was not accurate since the valve labeled as VR-053 on the P&ID, did not correspond to the identification tag of VR-052 observed in the field. q.Ammonium Phosphate Plant #100-Granualtion: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7011-F-122, was not accurate since the P&ID did not contain V-768 which was observed in the field. r.Ammonium Phosphate Plant #100-Granualtion: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7011-F-122, was not accurate since V- 768 was actually located downstream from the location indicated on the P&ID. s.Ammonium Phosphate Plant #100-Granualtion: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7011-F-122, was not accurate since the P&ID did not contain complete pipe labeling or size indications. Several pipe labels on the P&ID contained notes such as: "1/2 " AL-066-P??-??-?" or "?" ??-079-P???- ??-?". t.Ammonium Phosphate Plant #100-Granulation Building: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-7015-F-128.1, was not accurate since the valves labeled 773, 774, 783 and 784 on the P&ID, did not correspond to the identification tags observed in the plant. u.Ammonia Loading Dock: On or about January 5, 2011, and at times prior thereto, the P&ID marked as JRS-8555-F-100.1, was not accurate since piping labeled as "3" AL-SLA-904" on the P&ID was observed to be a four-inch line in the field. The J.R. Simplot Company, was previously cited for a violation of this occupational safety and health standard, which was contained in inspection number 314172024, citation 1, item 2A and was affirmed as a final order on November 8, 2010, with respect to a workplace located at 3630 Gateway Drive, Grand Forks, North Dakota. Note: Abatement certification and documentation are required for this item.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close