Violation Detail
Standard Cited: 19100303 B06 General.
Inspection Nr: 1838168.015
Citation: 02001A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $398.00
Current Penalty: $258.00
Issuance Date: 01/13/2026
Nr Instances: 5
Nr Exposed: 3
Abatement Date: 03/13/2026
Gravity:
Report ID: 0317900
Contest Date:
Final Order: 02/20/2026
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/20/2026 | $258.00 | 03/13/2026 | Other | |
| Penalty | Z: Issued | 01/13/2026 | $398.00 | 02/02/2026 | Other |
Text For Citation: 02 Item/Group: 001A Hazard:
29 CFR 1910.303(b)(6):Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures and were not identified for use in the operating environment: a) 40 WEST PARK AVENUE SELLERSVILLE, PA 18960, Large dip tank area, On or about July 18, 2025, and times prior to - Large 240 volts electrical disconnect, and other electrical components, were covered in rust from moisture, fumes , vapers or other deteriorating affects, were not identified for use in the operating environment. b) 40 WEST PARK AVENUE SELLERSVILLE, PA 18960 , Large dip tank area, On or about July 18, 2025, and times prior to - Large 480 volts electrical panel, and other electrical components, were covered in rust from moisture, fumes , vapers or other deteriorating affects, were not identified for use in the operating environment. c) 40 WEST PARK AVENUE SELLERSVILLE, PA 18960 , recycling tank/slug storage area, On or about July 18, 2025, and times prior to - Large 240 volts electrical panel, and other electrical components, were covered in rust from moisture, fumes , vapers or other deteriorating affects, were not identified for use in the operating environment. d)40 WEST PARK AVENUE SELLERSVILLE, PA 18960 , pump /drain room, On or about July 18, 2025, and times prior to -electrical panel, and other electrical components, were covered in rust from moisture, fumes , vapers or other deteriorating affects, were not identified for use in the operating environment. e) N40 WEST PARK AVENUE SELLERSVILLE, PA 18960 , small dip tank area in rear of building , On or about July 18, 2025, and times prior to -electrical panel, and other electrical components, were covered in rust from moisture, fumes , vapers or other deteriorating affects, were not identified for use in the operating environment.
Translate