Standard Cited: 19100303 G01 I General.
Inspection Nr: 1793560.015
Citation: 02001A
Citation Type: Other
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/05/2025
Nr Instances: 7
Nr Exposed: 8
Abatement Date: 03/04/2025
Gravity:
Report ID: 0111100
Contest Date: 02/24/2025
Final Order:
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 02/27/2025 | $0.00 | 03/04/2025 | Other | |
Penalty | Z: Issued | 02/05/2025 | $0.00 | 03/04/2025 | Other |
Text For Citation: 02 Item/Group: 001A Hazard:
29 CFR 1910.303(g)(1)(i): Workspace was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: Employer did not maintain 30 inches of space in front of electrical equipment, in the following instances: a) Maintenance Shop - The 220-volt knife switch used to operate the Speedaire upright compressor. b) Forklift Charging Area - Multiple (6) knife switches used to power multiple charging stations were blocked by a forklift charger.