Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1194726.015
Citation: 02001A
Citation Type: Repeat
Abatement Date: 06/12/2017
Initial Penalty: $49,797.00
Current Penalty: $0.00
Issuance Date: 05/08/2017
Nr Instances: 4
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0216000
Contest Date: 05/25/2017
Final Order: 02/07/2019
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/07/2019 | $0.00 | 06/12/2017 | Repeat | |
Penalty | C: Contested | 05/31/2017 | $49,797.00 | 06/12/2017 | Repeat | |
Penalty | Z: Issued | 05/08/2017 | $49,797.00 | 06/12/2017 | Repeat |
Text For Citation: 02 Item/Group: 001A Hazard:
29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process did not include piping and instrument diagrams: a) Anhydrous Ammonia Refrigeration System - Covered Process: The employer's P&ID did not include information pertaining to the equipment in the process as the oil trap tanks present on Vogt Ice Makers IM-1, IM-2, IM-3, IM-4, IM-5, IM-6, Im-7, and IM-8 were not identified; on or about 12/19/2016. b) Ammonia Refrigeration System - Covered Process: The employer's P&ID did not include information pertaining to the equipment in the process as the set pressure on the pressure relief valve for the oil separator on RC-5 was noted as 350 psig when it was actually set at 300 psig; on or about 12/19/2016. c) Ammonia Refrigeration System - Covered Process: The employer's P&ID did not include information pertaining to the equipment in the process as the set pressure on the pressure relief valve for the oil separator on RC-6 was noted as 350 psig when it was actually set at 300 psig; on or about 12/19/2016. d) Ammonia Refrigeration System - Covered Process: The employer's P&ID did not include information pertaining to the equipment in the process as the maximum allowable working pressure (MAWP) for the Vogt Ice Maker IM-4 was noted to be 200 psig when it was actually 275 psig; on or about 12/19/2016. REPEAT STATEMENT: Arctic Glacier U.S.A., Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29CFR 1910.119(d)(3)(i)(B), which was contained in OSHA inspection number 623559, citation number 1, item number 8a and was affirmed as a final order on June 28, 2013, with respect to a workplace located at 500 Fenimore Road, Mamaroneck, NY 10543.