Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 993351.015
Citation: 02001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/03/2015
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 03/21/2015
Gravity:
Report ID: 0215800
Contest Date: 03/20/2015
Final Order: 03/31/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 03/31/2016 | $0.00 | 03/21/2015 | Other | |
Penalty | C: Contested | 03/25/2015 | $0.00 | 03/21/2015 | Other | |
Penalty | Z: Issued | 03/03/2015 | $0.00 | 03/21/2015 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) 473 Hub Pit Area, on or about 11/4/14: Flexible cord was used as a substitute for the fixed wiring of a 440 volt blower unit. b) Elastomer Shop, on or about 10/2/14: A Relocatable Power Tap was used as an extension cord to provide power to a drill press and an industrial scale. c) Decorating Room - Column K18, on or about 10/3/14: A Relocatable Power Tap was used as an extension cord to provide power to a wall fan and an industrial microwave. d) Screen Cleaning Room, on or about 10/21/14: A Relocatable Power Tap was used as an extension cord to provide power to a sand blaster machine.