Standard Cited: 19100119 J05 Process safety management of highly hazardous chemicals.

Inspection Nr: 313030306

Citation: 02001

Citation Type: Repeat

Abatement Status: X

Initial Penalty: $35,000.00

Current Penalty: $7,000.00

Issuance Date: 10/27/2010

Nr Instances: 2

Nr Exposed: 2

Abatement Date: 11/15/2010

Gravity: 10

Report ID: 0625700

Contest Date: 11/08/2010

Final Order: 08/12/2011

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty J: ALJ Decision 08/12/2011 $7,000.00 11/15/2010 Repeat  
Penalty Z: Issued 10/27/2010 $35,000.00 11/15/2010 Repeat  

Text For Citation: 02 Item/Group: 001 Hazard: REFINERY

29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (as defined by process information in 29 CFR 1910.119(d)) before further use or in a safe and timely manner: a) The employer does not ensure that all pressure gauges and indicator lights on emergency isolation valve panel boards are operational. Throughout the H-Oil Unit there are isolation valve panel boards such as, but not limited to, LCB 101, LCB-102, LCB-103, LCB-201, LCB-301, LCB-302, and LCB 401 with non-functioning indicator lights and broken and/or faulty pressure gauges. As a result of this condition, Outside Operators are unable to properly identify which valves are open or close by viewing the panel board and in the event of an emergency would have to physically check the valves throughout the unit, exposing them to a fire and/or explosion hazards. This hazard was most recently observed on or about May 5, 2010 and July 20, 2010 at Motiva Enterprises LLC, Convent, LA. b) The employer does not ensure that corroded/rusted out drain block valves and drain piping for H-Oil vessel 70F-312 (Second Stage Compressor Knockout Drum) are repaired and/or replaced for safe operation. This hazard was most recently observed on or about July 20, 2010 and August 25, 2010 at Motiva Enterprises LLC, Convent, LA. Pursuant to 29 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that all deficient equipment is in fully operational condition. The violation must be abated no later than 30 days from receipt of this citation. MOTIVA ENTERPRISES LLC WAS PREVIOUSLY CITED FOR A VIOLATION OF THE THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD 1910.119(j)(5) WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 311522601, CITATION NUMBER 1, ITEM NUMBER 8, ISSUED ON AUGUST 21, 2008, WITH RESPECT TO A WORKPLACE LOCATED AT 15536 RIVER RD, NORCO, LA 70079.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close