Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1693692.015
Citation: 02001
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/16/2024
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity:
Report ID: 0213900
Contest Date: 03/13/2024
Final Order: 11/15/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 11/15/2024 | $0.00 | Other | ||
Penalty | C: Contested | 04/23/2024 | $0.00 | Other | ||
Penalty | Z: Issued | 02/16/2024 | $0.00 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Plant Floor Wet Side - Quality Control - The employer allowed employees to use a relocatable power tap (RPT) connected in series with an extension cord and not to a permanently installed branch circuit to energize a fan thereby not using the relocatable power tap in accordance with its listing and labeling, thus exposing employees to electrical and fire hazards. This condition was observed on or about October 26, 2023.