Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1676403.015
Citation: 02001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $491.00
Current Penalty: $0.00
Issuance Date: 09/12/2023
Nr Instances: 7
Nr Exposed: 2
Abatement Date: 10/16/2023
Gravity:
Report ID: 0111100
Contest Date:
Final Order: 09/29/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/29/2023 | $0.00 | 10/16/2023 | Other | |
| Penalty | Z: Issued | 09/12/2023 | $491.00 | 09/29/2023 | Repeat |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts were less than indicated in Table S-1 of Subpart S: Electric equipment did not have the required depth of the working space to live parts as indicated in Table S-1 of Subpart S, in the following instances: a) KL's Office - Panel CO2. b) Main Entrance, Receptionist Service Area - Panel LE. c) Balsam Office - Panel CD. d) Maintenance Room - E-1 Emergency Generator disconnect. e) Maintenance Room - Heat Pump #1 PUMP #1 disconnect. f) Maintenance Room - Panel E-1 PUMP #1 disconnect. g) Maintenance Room - #1 Boiler disconnect. Genesis Healthcare was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 1357088, citation number 1, item number 2, and was affirmed as a final order on February 14, 2019, with respect to a workplace located at 32 Hospital Street, Gardner, MA 01440.
Translate