Violation Detail
Standard Cited: 19100303 B07 General.
Inspection Nr: 1670004.015
Citation: 02001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/03/2023
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 11/01/2023
Gravity:
Report ID: 0418200
Contest Date:
Final Order: 11/20/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/20/2023 | $0.00 | 11/01/2023 | Other | |
| Penalty | Z: Issued | 10/03/2023 | $0.00 | 11/01/2023 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner: a) Slear #1: On or about , May 11, 2023, and at times prior, the employer exposed employees to electric shock hazards, in that electrical conductors and conduit were not installed in a neat and workmanlike manner, in that electrical conductors were run through two different types of conduit with a gap between the conduits exposing the insulated wires and the weight of the conduit which was not secured to building or equipment surfaces where elevated above the floor, was supported by the enclosed conductors.