Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1663647.015
Citation: 02001
Citation Type: Other
Abatement Date: 01/02/2024 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/29/2023
Nr Instances: 2
Nr Exposed: 40
Related Event Code (REC):
Gravity:
Report ID: 0215800
Contest Date:
Final Order: 11/01/2023
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 12/15/2023 | $0.00 | 01/02/2024 | Other | |
Penalty | I: Informal Settlement | 11/01/2023 | $0.00 | 01/02/2024 | Other | |
Penalty | Z: Issued | 09/29/2023 | $0.00 | 11/17/2023 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams did not include information that provided specific identification of equipment that is part of the process: a) On or about 4/5/2023, Anhydrous Ammonia Refrigeration System: The existing P&ID's had discrepancies between the drawings and what was actually in place, such as, but not limited to: 1) P&IDs showed a 2" HPL at the Accumulator, while in actuality there was a 3" HPL. 2) P&ID show that the self closing valves for the oil pots in cellar W were equipped with caps while in reality there were no caps. Abatement certification is required for this item.