Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1575625.015
Citation: 02001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/29/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 08/10/2022
Gravity:
Report ID: 0336000
Contest Date:
Final Order: 08/17/2022
Related Event Code (REC): A;R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/17/2022 | $0.00 | 08/10/2022 | Other | |
Penalty | Z: Issued | 07/29/2022 | $0.00 | 08/10/2022 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Lowbucs Propane, Inc., On or about January 31st, 2022 and times prior thereto: An electrical panel box located to the northeast of the fill station area, contained breakers for electrical circuits including, but not limited to, propane pumps, and fill house lights. Not all the breakers within the electrical panel box were identified as to their function at the panel box location. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.