Violation Detail
Standard Cited: 19100303 G01 General.
Inspection Nr: 1568435.015
Citation: 02001
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/16/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity:
Report ID: 0521400
Contest Date:
Final Order: 03/15/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/15/2022 | $0.00 | Other | ||
| Penalty | Z: Issued | 02/16/2022 | $0.00 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. Production Area, Near East Exit Door. On or about December 14, 2021, the employer did not maintain at least 36 inches of clear space in front of electrical disconnect boxes up to 240V. Access to working space and shutoff in the event of an emergency was partially blocked by storage of a machine cabinet. There is no abatement documentation or certification required for this item.