Violation Detail
Standard Cited: 19100137 C02 VIII Electrical protective equipment.
Inspection Nr: 1446937.015
Citation: 02001
Citation Type: Other
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/25/2020
Nr Instances: 1
Nr Exposed: 12
Related Event Code (REC):
Gravity:
Report ID: 0522500
Contest Date:
Final Order: 04/20/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 03/25/2020 | $0.00 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5. a. On or about November 22, 2019, employees performed electrical work with one set of rubber insulated gloves that were dated with their last electrical test in February 2014 and another set tested on March 23, 2018. The employer did not ensure the rubber insulated gloves were tested at least every six months.