Violation Detail
Standard Cited: 19100023 D02 Ladders.
This violation item has been deleted.
Inspection Nr: 1441704.015
Citation: 02001
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/08/2020
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity:
Report ID: 0111700
Contest Date:
Final Order: 05/05/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/05/2020 | $0.00 | Other | ||
Penalty | Z: Issued | 04/08/2020 | $0.00 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.23(d)(2): (2) The minimum perpendicular distance from the centerline of the steps or rungs, or grab bars, or both, to the nearest permanent object in back of the ladder was not 7 inches: Boiler room- The fixed ladder used to access the storage area over the boiler room had 3.5 inches of clearance between the top ladder rung and the wall on which it was mounted. The ladder rungs below the top rung had 6 inches of clearance between the rungs and the wall on which it was mounted.