Violation Detail
Standard Cited: 19101025 E04 I Lead.
This violation item has been deleted.
Inspection Nr: 1294470.015
Citation: 02001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/13/2018
Nr Instances: 1
Nr Exposed: 21
Abatement Date: 09/28/2018
Gravity:
Report ID: 0524530
Contest Date: 09/05/2018
Final Order: 01/06/2020
Related Event Code (REC):
Emphasis:
Substance: 1591
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/06/2020 | $0.00 | 09/28/2018 | Other | |
Penalty | C: Contested | 09/07/2018 | $0.00 | 09/28/2018 | Other | |
Penalty | Z: Issued | 08/13/2018 | $0.00 | 09/28/2018 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.1025(e)(4)(i): When ventilation was used to control exposure to lead, measurements which demonstrate the effectiveness of the system in controlling exposure were not made at least every three months: The employer did not ensure that when local exhaust ventilation systems used to control employee exposure to lead, measurements which demonstrate the effectiveness of the system were made at least every three months. Such measurements may include, but are not limited to, capture velocity, duct velocity, and static pressure.