Violation Detail
Standard Cited: 19100303 G01 I General.
Inspection Nr: 1222325.015
Citation: 02001
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/19/2017
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity:
Report ID: 0523400
Contest Date:
Final Order: 08/07/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/07/2017 | $0.00 | Other | ||
Penalty | Z: Issued | 07/19/2017 | $0.00 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1: (a) In the Electrical Room, the clearance space in front of two 240 volt circuit breaker panels was limited to 23 inches due to a work bench that was positioned in front of it.