Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1212648.015
Citation: 02001
Citation Type: Repeat
Abatement Date: 09/05/2017 2
Initial Penalty: $63,375.00
Current Penalty: $0.00
Issuance Date: 07/31/2017
Nr Instances: 1
Nr Exposed: 37
Related Event Code (REC): R
Gravity: 10
Report ID: 0626700
Contest Date:
Final Order: 09/15/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/15/2017 | $0.00 | 09/05/2017 | Repeat | |
Penalty | Z: Issued | 07/31/2017 | $63,375.00 | 09/05/2017 | Repeat |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience. On or about February 12, 2017, and at times prior to, in the Sulfur Recovery Unit at Houston Refining in Houston, TX, the employer did not ensure that the frequency of inspections and testing of process piping was performed in accordance with Recognized and Generally Accepted Good Engineering practices such as but not limited to API RP 570 (Piping Inspection Code: In-service Inspection, Rating, Repair, and Alteration of Piping Systems), when: a) The employer failed to inspect piping circuit 42-TG-1023-CAD (ISO439-0038-04), at the designated 5 year inspection interval (API RP 570, Table 2) at the following locations: 1. TML 1 2. TML 2 3. TML 3 4. TML 4 5. TML 5 6. TML 6 7. TML 7 8. TML 8 9. TML 9 10. TML 10 11. TML 11 12. TML 12 13. TML 13 14. TML 14 15. TML 15 16. TML 16 17. TML 17 b) After the piping was placed in service, subsequent measurements of 42-TG-1023-CAD (ISO439-0038-04), were not made at appropriate intervals to establish short and/or long term corrosion (API RP 570 Section 7.1.2), at the following locations: 1. TML 1 2. TML 3 3. TML 4 4. TML 5 5. TML 6 6. TML 8 7. TML 9 8. TML 10 9. TML 11 10. TML 12 11. TML 14 12. TML 15 13. TML 16 14. TML 17 c) Corrosion under insulation (CUI) inspection was not performed on piping circuit 42-TG-1023-CAD (ISO439-0038-04) to monitor corrosion (API RP 570 Section 6.4), at the following locations: 1. TML 1 2. TML 2 3. TML 3 4. TML 4 5. TML 5 6. TML 6 7. TML 7 8. TML 8 9. TML 9 10. TML 10 11. TML 11 12. TML 12 13. TML 13 14. TML 14 15. TML 15 16. TML 16 17. TML 17 Houston Refining, LP was previously cited for a violation for this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.119(j)(4)(iii) which is contained in OSHA Inspection Number 1139040, Citation Number 1 item 1b, issued on September 15, 2016 with respect to a workplace located at 12000 Lawndale, Houston, TX. This file became final order on February 29, 2017.